AutoDoor Atlas

Battery Backup Runtime

How long will this automatic-door or access-control system operate on battery backup under realistic use?

More than amp-hours divided by amps

Continuous mode is for loads that stay on. Automatic-door mode weights standby current against total current while the door is moving, using openings per hour and seconds per cycle. Adjusted runtime applies the usable-capacity factor you enter.

Load model

Use this when the door sits in standby and draws more current only while it is moving.

Wiring

Series adds voltage. Parallel adds Ah. Do not add Ah in series.

Field result

Battery bank24.0 V · 7.00 Ah
Usable capacity5.60 Ah (80.0%)
Standby current0.20 A
Operating current2.00 A
Openings / hour60
Duty cycle10.0%
Average load0.38 A
Theoretical runtime18 h 25 min
Adjusted runtime14 h 44 min
Estimated door cycles884

Series versus parallel

Two 12 V 7 Ah batteries in series make a 24 V 7 Ah bank. The same two in parallel make a 12 V 14 Ah bank. Amp-hours are not added in series.

FAQ

Is operating current extra current above standby?
No. Enter the total current while the door is moving. The average-current model already weights standby time and operating time so standby is not counted twice.
Does this prove emergency-egress runtime?
No. It is a field estimate. Age, temperature, chemistry, and actual motor load change runtime.