Battery Backup Runtime
How long will this automatic-door or access-control system operate on battery backup under realistic use?
More than amp-hours divided by amps
Continuous mode is for loads that stay on. Automatic-door mode weights standby current against total current while the door is moving, using openings per hour and seconds per cycle. Adjusted runtime applies the usable-capacity factor you enter.
Field result
Battery bank24.0 V · 7.00 Ah
Usable capacity5.60 Ah (80.0%)
Standby current0.20 A
Operating current2.00 A
Openings / hour60
Duty cycle10.0%
Average load0.38 A
Theoretical runtime18 h 25 min
Adjusted runtime14 h 44 min
Estimated door cycles884
Series versus parallel
Two 12 V 7 Ah batteries in series make a 24 V 7 Ah bank. The same two in parallel make a 12 V 14 Ah bank. Amp-hours are not added in series.
FAQ
- Is operating current extra current above standby?
- No. Enter the total current while the door is moving. The average-current model already weights standby time and operating time so standby is not counted twice.
- Does this prove emergency-egress runtime?
- No. It is a field estimate. Age, temperature, chemistry, and actual motor load change runtime.